Last Updated: 3/3/2003 |
| |
|
| Devices Supported: |
All Modbus RTU compatible devices |
| Profile Name: |
MODBUS.PRO |
| Profile Built For: |
UOS |
| Platform: |
Windows NT4.0 / 2000 / XP |
| Interface Type: |
Device Specific |
| Max Devices
Supported: |
31 |
| Protocol: |
Modbus RTU |
| Baud Rates: |
110, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 |
| Data Bits: |
7, 8 |
| Stop Bits: |
1, 2 |
| Parity: |
NONE, EVEN, ODD |
| Comment: |
UMB is comprised of the Universal OPC
Server (UOS) for Serial and TCP/IP Devices and the MODBUS.PRO device
profile. The UMB mnemonic is used to identify this unique combination. UOS will also
support many other serial or TCP/IP device profiles. Please refer to our web site for the
current list. |
|
UOS is a stand-alone OPC Server that can be used
with any OPC compliant Client such as Intellutions FIX® or FIX Dynamics®
or OAs Enterprise Automation software. UOS has many advanced features like:
DataView, DataScope, Serial and TCP/IP communications support, and multiple
"different" device support. Please refer to our web site for more information on
UOS capabilities. |
| Contact: |
Dimension
Software, Inc. - 1536 St. Clair Road, Taylorsville, NC 28681, USA
- Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: dsi@caro.net Web: http://www.caro.net/dsi. |
| References: |
UOS (Universal OPC Server)
Electronic Documentation |
| |
| Flow Control:
specifies the type of hardware handshaking allowed. Handshaking is only valid if supported
by the interface module. This value must match the value used by the field device that
this channel is communicating with in order to establish communication. Legal entries are: |
|
- None
- RTS/CTS
- DTR/DSR
- RTS Delay
|
| RTS Delay can be used in special applications
where control of the RTS line is necessary. When RTS Delay is selected the RTS Delay area
(located to the right of the Flow Control drop-down menu) becomes active. The table below
shows the range in milli-seconds associated with each parameter. The msec value entered
must be a multiple of 10msec. |
| Signal Conditioning
Name: |
Description: |
| NONE |
No Scaling |
| LIN (Unsigned) |
Scales 16-bit unsigned values to the database block's EGU
range. |
| LIN (Signed) |
Scales 16-bit signed values to the database block's EGU
range. |
| 3BCD |
Scales 3-digit Binary Coded Decimal values to the database
block's EGU range. |
| 4BCD |
Scales 4-digit Binary Coded Decimal values to the database
block's EGU range. |
| 8BN |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. No Alarming on Out of Range. |
| 8AL |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. Alarming on Out of Range. |
| 12BN |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). No Alarming on Out of
Range. |
| 12AL |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). Alarming on Out of
Range. |
| 13BN |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. No Alarming on Out of Range. |
| 13AL |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. Alarming on Out of Range. |
| 15BN |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. No Alarming on Out of Range. |
| 15AL |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. Alarming on Out of Range. |