Last Updated: 3/3/2003 |
| |
|
| Devices Supported: |
Advantech ADAM 4000 Series I/O Modules |
| Device Manufacturer: |
American Advantech Corp., 750 East Arques Av., Sunnyvale, CA
94086 U.S.A., Tel: (408)522-4697 FAX: (408)245-8268 |
| Profile Name: |
ADAM.PRO |
| Profile Built For: |
UOS |
| Platform: |
Windows NT4.0 / 2000 / XP |
| Interface Type: |
Serial: RS-485. ADAM-4520 RS-232 to RS-485 converter was used
during testing. Also tested Telebyte Model 285 converter. |
| Max Devices Supported: |
31 |
| Protocol: |
ADAM 4000 |
| Comment: |
UAD is comprised of the Universal OPC
Server (UOS) for Serial and TCP/IP Devices and the ADAM.PRO device
profile. The UAD mnemonic is used to identify this unique combination. UOS will also
support many other serial or TCP/IP device profiles. Please refer to our web site for the
current list. |
|
UOS is a stand-alone OPC Server that can be used with any OPC
compliant Client such as Intellutions FIX® or FIX Dynamics® or
OAs Enterprise Automation software. UOS has many advanced features like: DataView,
DataScope, Serial and TCP/IP communications support, and multiple "different"
device support. Please refer to our web site for more information on UOS capabilities. |
| Contact: |
Dimension
Software, Inc. - 1536 St. Clair Road, Taylorsville, NC 28681, USA
- Voice: (828) 635-7189, Fax: (828) 625-5319,
E-Mail: dsi@caro.net Web: http://www.caro.net/dsi. |
| References: |
UOS (Universal OPC Server) Electronic
Documentation |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4011$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4011#AA_AI |
#AA_AI |
n/a |
Read Analog Inputs |
| 4011@AADI/@AADO |
@AADI |
@AADO |
Read Alarm state and Digital input ports. Read/Write Digital output ports |
| 4011@AAEAT |
n/a |
@AAEAT |
Set Alarm type |
| 4011@AADA |
n/a |
@AADA |
Disables all alarm functions . |
| 4011@AARH/@AAHI |
@AARH |
@AAHI |
Read/Write High Alarm |
| 4011@AARL/@AALO |
@AARL |
@AALO |
Read/Write Low Alarm |
| 4011@AARE |
@AARE |
n/a |
Read Stored Value of Event counter |
| 4011@AACE |
n/a |
@AACE |
Resets event counter to 0. |
| 4011#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4011$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4011@AACA |
n/a |
@AACA |
Clears latched alarms. |
| 4011$AA0 |
n/a |
$AA0 |
Span Calibration |
| 4011$AA1 |
n/a |
$AA1 |
Offset Calibration |
| 4011$AA3 |
$AA3 |
n/a |
Read CJC Status |
| 4011$AA9 |
n/a |
$AA9 |
CJC Offset Calibration |
| 4011$AAF |
$AAF |
n/a |
Read Firmware Version Number |
| 4011$AAM |
$AAM |
n/a |
Read Module Number |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4012$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4012#AA_AI |
#AA_AI |
n/a |
Read Analog Inputs |
| 4012@AADI/@AADO |
@AADI |
@AADO |
Read Alarm state and Digital input ports. Read/Write Digital output ports |
| 4012@AAEAT |
n/a |
@AAEAT |
Set Alarm type. |
| 4012@AAHI |
n/a |
@AAHI |
Set high alarm limit. |
| 4012@AALO |
n/a |
@AALO |
Set low alarm limit. |
| 4012@AADA |
n/a |
@AADA |
Disables all alarm functions . |
| 4012@AARH |
@AARH |
n/a |
Read high alarm limit in engineering units. |
| 4012@AARL |
@AARL |
n/a |
Read low alarm limit in engineering units. |
| 4012@AARE |
@AARE |
n/a |
Stored value of the event counter. |
| 4012@AACE |
n/a |
@AACE |
Resets event counter to 0. |
| 4012#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4012$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4012@AACA |
n/a |
@AACA |
Clears latched alarms. |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4017$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4017$AA0 |
n/a |
$AA0 |
Span Calibration |
| 4017$AA1 |
n/a |
$AA1 |
Offset Calibration |
| 4017#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4017$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4017$AA5 |
$AA5 |
n/a |
Read reset status. |
| 4017$AAF |
$AAF |
n/a |
Read Firmware Version Number |
| 4017$AAM |
$AAM |
n/a |
Read Module Number |
| 4017#AAN |
#AAN |
n/a |
Read Analog Input from Channel N |
| 4017$AA5VV/$AA6 |
$AA5VV |
/$AA6 |
Read Channel Status or Enable/Disable Channels for Multiplexing |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4021$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4021#AA_AO |
n/a |
#AA_AO |
Write analog output |
| 4021$AA6 |
$AA6 |
n/a |
Latest output value received from the Analog Data Out command. |
| 4021$AA8 |
$AA8 |
n/a |
Read current flowing through its current/voltage loop. |
| 4021$AA5 |
$AA5 |
n/a |
Read reset status. |
| 4021$AA4 |
n/a |
$AA4 |
Start-Up Output Current/Voltage Congfuration. |
| 4021$AA3 |
n/a |
$AA3 |
Trims specific module a number of units up/down. |
| 4021$AA0 |
n/a |
$AA0 |
4mA Calibration |
| 4021$AA1 |
n/a |
$AA1 |
20mA Calibration |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4050$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4050$#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4050$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4050$AA5 |
$AA5 |
n/a |
Read reset status. |
| 4050$AA6 |
$AA6 |
n/a |
Read values of input and output channels. |
| 4050$AA6_#AABB_RW_8CH |
$AA6 |
#AABB |
Read all digital input channels. Read and write all digital output
channels |
| 4050#AABB_WSDO |
n/a |
#AABB |
Write single digital output channel. |
| 4050$AAF |
$AAF |
n/a |
Read Firmware Version Number |
| 4050$AAM |
$AAM |
n/a |
Read Module Number |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4052$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4052$#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4052$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4052$AA5 |
$AA5 |
n/a |
Reset Status of the Addressed Digital Input Module |
| 4052$AAF |
$AAF |
n/a |
Read Firmware Version Number |
| 4052$AAM |
$AAM |
n/a |
Read Module Number |
| If the UAD Command Group is... |
The READ command is... |
And the WRITE command is... |
And the command group description is... |
| 4053$AA2/ AANNTTCCFF |
$AA2 |
AANTTCCFF |
Read/Write Device Address, Baud Rate, Input Range Code, etc. |
| 4050$#** |
n/a |
#** |
Perform Synchronized Sampling |
| 4050$AA4 |
$AA4 |
n/a |
Read synchronized data and status. |
| 4050$AA5 |
$AA5 |
n/a |
Read reset status. |
| 4050$AA6 |
$AA6 |
n/a |
Read values of 16 input channels. |
| 4052$AAF |
$AAF |
n/a |
Read Firmware Version Number |
| 4052$AAM |
$AAM |
n/a |
Read Module Number |
| Signal Conditioning
Name: |
Description: |
| NONE |
No Scaling |
| LIN (Unsigned) |
Scales 16-bit unsigned values to the database block's EGU
range. |
| LIN (Signed) |
Scales 16-bit signed values to the database block's EGU
range. |
| 3BCD |
Scales 3-digit Binary Coded Decimal values to the database
block's EGU range. |
| 4BCD |
Scales 4-digit Binary Coded Decimal values to the database
block's EGU range. |
| 8BN |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. No Alarming on Out of Range. |
| 8AL |
Scales 8-bit binary values to the database block's EGU
range. Ignores the most significant byte. Alarming on Out of Range. |
| 12BN |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). No Alarming on Out of
Range. |
| 12AL |
Scales 12-bit binary values to the database block's EGU
range. Ignores the most significant nibble (4-bits). Alarming on Out of
Range. |
| 13BN |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. No Alarming on Out of Range. |
| 13AL |
Scales 13-bit binary values to the database block's EGU
range. Ignores the most significant 3 bits. Alarming on Out of Range. |
| 15BN |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. No Alarming on Out of Range. |
| 15AL |
Scales 15-bit binary values to the database block's EGU
range. Ignores the most significant bit. Alarming on Out of Range. |