Modbus TCP / Modbus Plus  (MBT)

OPC Server Data Sheet

 

Last Updated: 3/3/2003

 

 

Devices Supported:

Modicon Quantuam, Premium, Atrium, and Momentum PLCs. Also communicates with any device that uses standard Modbus/TCP or Modbus Plus Protocol.

Performance:

Performance data provided on request.  Please email dsi@caro.net. MBT will out-perform all Modbus Ethernet servers on the market.

OPC Compliance:

OPC 2.04 and OPC 1.0a Data Access

Platform:

Windows NT4.0 / 2000 / XP

Interface Type:

Modbus Ethernet and Modbus Plus in one OPC Server

Protocol:

Modbus/Ethernet, Modbus Plus

Modbus Addressing:

4, 5, or 6 digits (Modbus Ethernet and Modbus Plus)

Data Types:

ASCII, Signed Integer, Unsigned Integer, Float, Digital, Time, Long, Signed Long

Contact:

Dimension Software, Inc. - 1536 St. Clair Road, Taylorsville, NC 28681, USA - Voice: (828) 635-7189, Fax: (828) 625-5319, E-Mail: dsi@caro.net Web: http://www.caro.net/dsi.

 

 

General Features

 

 

1

A user interface called the PowerTool for configuring channels, devices, and datablocks.  Statistical communications data is provided for throughput analysis at each level.

2

The PowerTool has a built-in datascope for checking Host-to-RTU and RTU-to-Host communications messages.  The PowerTool also has context sensitive help.

3

Direct, Radio, and Telephone communication modes.

4

Automatic reads after a write to confirm a write.

5

Automation Interface - You don't have to use the Power Tool to configure the driver.  You can make your own COM or OLE application (using Microsoft's Visual Basic) to configure the driver and access data.

6

Secondary Poll Rate - The OPC Server polls a datablock at the secondary poll rate once the Access Time expires.  Data is polled at the secondary poll rate until there is another client request for data.  If  the secondary poll rate is set for a longer period of time than the Primary Rate, CPU resources are reduced while ensuring that the datablock will always be polled.

7

Phased Poll Rates

8

Enable/Disable individual communication channels, devices, and datablocks from the automation interface or your HMI.

 

 

Modbus Ethernet Features

 

 

1

Supports redundant Modbus Ethernet networks.

2

Supports multiple simultaneous connections to the same device.

3

Supports redundant devices (devices can have the same IP address, port, and unit ID).

 

 

Modbus Plus Features

 

 

1

Supports redundant Modbus Plus networks.

2

Supports use of multiple master paths.

3

Supports redundant devices (devices can have the same routing path).

4

Supports global data, including writing to local node global data.

 

 

 

Function Codes Supported (Modbus Ethernet and Modbus Plus)

 

 

Memory Type:

Function Code:

Command Name:

Data Type Supported:

Coil

1

Read Coil

Bool Only

 

5

Write Coil

Bool Only

 

15

Force Multiple Coils

Bool Only

Holding Register

3

Read Multiple Registers

All

 

6

Write Single Register

All

 

16

Write Multiple Registers

All

Input Discrete / Status

2

Read Input Discrete

Bool Only

Input Register

4

Read Input Registers

All

Exception Status

7

Read Exception Status

Bool Only

Extended Register

20

Read General Reference

All

 

21

Write General Reference

All

FIFO

24

Read FIFO

All

 

 

Addresses Ranges (Modbus Ethernet and Modbus Plus)

 

 

Memory Type:

Type:

Read/Write:

Address Type:

Address Range:

Maximum Length:

Coil

Digital

R/W

4 Digit

1 - 999

800

 

 

 

5 Digit

1 - 9999

 

 

 

 

6 Digit

1 - 65536

 

Holding Register

Analog

R/W

4 Digit

4001 - 4999

125

 

 

 

5 Digit

40001 - 49999

 

 

 

 

6 Digit

400001 - 465536

 

Input Discrete

Digital

R

4 Digit

1001 - 1999

800

 

 

 

5 Digit

10001 - 19999

 

 

 

 

6 Digit

100001 - 165536

 

Input Register

 

 

4 Digit

3001 - 3999

125

 

 

 

5 Digit

30001 - 39999

 

 

 

 

6 Digit

300001 - 365536

 

Exception Status

Digital

R

Any

EX:1 - EX:8

8

Extended Register

Analog

R/W

4 Digit

6000:1 - 6999:10

125

 

 

 

5 Digit

60000:1 - 69999:10

 

 

 

 

6 Digit

600000:1 - 665535:10

 

FIFO

Analog

R

4 Digit

FF:1 - FF:999

32

 

 

 

5 Digit

FF:1 - FF:9999

 

 

 

 

6 Digit

FF:1 - FF:65536

 

 

 

Signal Conditioning:

 

 

Signal Conditioning Name:

Description:

NONE

No Scaling

LIN (Unsigned)

Scales 16-bit unsigned values to the database block's EGU range.

LIN (Signed)

Scales 16-bit signed values to the database block's EGU range.

3BCD

Scales 3-digit Binary Coded Decimal values to the database block's EGU range.

4BCD

Scales 4-digit Binary Coded Decimal values to the database block's EGU range.

8BN

Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. No Alarming on Out of Range.

8AL 

Scales 8-bit binary values to the database block's EGU range. Ignores the most significant byte. Alarming on Out of Range.

12BN

Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). No Alarming on Out of Range.

12AL 

Scales 12-bit binary values to the database block's EGU range. Ignores the most significant nibble (4-bits). Alarming on Out of Range.

13BN

Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. No Alarming on Out of Range.

13AL 

Scales 13-bit binary values to the database block's EGU range. Ignores the most significant 3 bits. Alarming on Out of Range.

15BN

Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. No Alarming on Out of Range.

15AL 

Scales 15-bit binary values to the database block's EGU range. Ignores the most significant bit. Alarming on Out of Range.

 

 